CVE-2022-30316
UNKNOWN

CVE-2022-30316

Published Jul 28, 2022 · Updated Nov 3, 2026

Severity · CVSSUNKNOWN · Not scored
Known exploitationNot listed
EPSS / likelihood0.38%
QFinch risk scoreNot available

Original summary

Normalized public record · Updated Nov 3, 2026

Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthenticated firmware update issue. The affected components are characterized as: Firmware update functionality. The potential impact is: Firmware manipulation. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 communication FTA serial interface and Enea POLO bootloader for firmware management purposes. An engineering workstation running the Safety Builder software communicates via serial or serial-over

Publisher and source text is retained separately from QFinch interpretation.

QFinch assessment

Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthenticated firmware update issue. The affected components are characterized as: Firmware update functionality. The potential impact is: Firmware manipulation. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 communication FTA serial interface and Enea POLO bootloader for firmware management purposes. An engineering workstation running the Safety Builder software communicates via serial or serial-over-ethernet link with the DCOM-232/485 interface. Firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks. Firmware images are unsigned. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize hardcoded credentials (see FSCT-2022-0052) for the POLO bootloader to control the boot process and push malicious firmware images to the controller allowing for firmware manipulation, remote code execution and denial of service impacts. A mitigating factor is that in order for a firmware update to be initiated, the Safety Manager has to be rebooted which is typically done by means of physical controls on the Safety Manager itself. As such, an attacker would have to either lay dormant until a legitimate reboot occurs or possibly attempt to force a reboot through a secondary vulnerability.

Evidence: public source records

Affected products

Affected scope reported by the available public evidence
Affected package, product or rangeFix status
Consult the referenced vendor advisory for affected versions.Consult source advisory

Matching a version is only one part of assessing exposure. QFinch has not assessed your environment on this public page.

Remediation

Apply the vendor-supported fixed release or mitigation, then verify the affected component is no longer reachable.

  1. Confirm the affected product and reachable code path exist in your environment.
  2. Apply the vendor-supported patch or mitigation from the primary advisory.
  3. Rescan the exact deployed revision and retain verification evidence.
Review primary references

Evidence coverage

FIRST-EPSSCVE-LIST-V5
SSVC priority
LOW
Confidence
Not available
Aliases
None reported